Where Do I Install Those Pesky Fire Alarm Pull Boxes?

Where should the pull station be located in relationship to an exit?

The California Fire Code (CFC) states that manual fire alarm boxes must be located not more than 5 feet from the entrance to each exit. NFPA 72 further clarifies that manual fire alarm boxes shall be located within 5 feet (60 inches) of the exit doorway opening at each exit on each floor.

 

2007 California Fire Code Section 907.4.2 and NFPA 72-2002 Section 5.12.6
2010 California Fire Code Section 907.4.1 and NFPA 72-2010 Section 17.14.6
2013 California Fire Code Section 907.4.2.1 and NFPA 72-2013 Section 17.14.8.4
2016 California Fire Code (CFC) Section 907.4.2.1 and NFPA 72-2016 Section 17.14.8.4